Oil/gas fired low pressure hot water boiler Vitomax 100

  • Economical fuel consumption — boiler efficiency: 91.5%
  • Boiler with reversing combustion chamber with low combustion chamber loading (?Ь 1.2 MW/m3) ЁC clean combustion with low nitrogen oxide emissions
  • No minimum heating water flow rate required — wide water galleries and large water content provide excellent natural circulation and a reliable heat transfer — simplified hydraulic connection
  • No additional intermediate flow piece required. All necessary connections for a safety temperature of 110 єC are already fitted to the boiler
  • Low pressure drop on the hot gas side through convection heating surfaces with generously sized hot gas pipes
  • High level of serviceability through water-cooled reversing chamber without lining plus large cleaning door
  • Low radiation losses through 100 mm thick composite thermal insulation
  • Load bearing cover on top of the boiler as part of the standard delivery — this simplifies the installation and maintenance and protects the thermal insulation against accidental damage
  • The Vitocontrol control panel enables the regulation of all boiler-specific control equipment
  • Approval in accordance with the European Pressure Equipment Directive 97/23/EC or the Gas Equipment Directive 90/396/EEC


Oil/gas fired low pressure hot water boiler Vitomax 200

  • Economical fuel consumption — boiler efficiency: 91.5%
  • Boiler with reversing combustion chamber with low combustion chamber loading (?Ь 1.2 MW/m3) ЁC clean combustion with low nitrogen oxide emissions
  • No minimum heating water flow rate required — wide water galleries and large water content provide excellent natural circulation and a reliable heat transfer — simplified hydraulic connection
  • No additional intermediate flow piece required. All necessary connections for a safety temperature of 110 єC are already fitted to the boiler
  • Low pressure drop on the hot gas side through convection heating surfaces with generously sized hot gas pipes
  • High level of serviceability through water-cooled reversing chamber without lining plus large cleaning door
  • Low radiation losses through 100 mm thick composite thermal insulation
  • Load bearing cover on top of the boiler as part of the standard delivery — this simplifies the installation and maintenance and protects the thermal insulation against accidental damage
  • The Vitocontrol control panel enables the regulation of all boiler-specific control equipment
  • Approval in accordance with the European Pressure Equipment Directive 97/23/EC or the Gas Equipment Directive 90/396/EEC


Oil/gas-fired low pressure hot water boiler Vitomax 300

  • High operational reliability and a long service life through multi-layered convection heating surfaces made from Duplex pipes
  • Low energy consumption due to modulating boiler water temperature. Standard efficiency: 96 % (Hi). Standard efficiency improved by up to 10% through condensing technology with Vitotrans 300 stainless steel flue gas/water heat exchanger
  • Low minimum return temperature of 38°C when using fuel oil and 45°C when using gas
  • No minimum heating water flow rate required — wide water galleries and large water content provide excellent natural circulation and a reliable heat transfer — simplified hydraulic connection
  • No additional intermediate flow piece required. All necessary connections for a safety temperature of 110 єC are already fitted to the boiler
  • Low pressure drop on the hot gas side through convection heating surfaces with generously sized hot gas pipes
  • Low radiation losses through 120 mm thick composite insulation as well as water-cooled front and rear reversing chambers
  • Three-pass boiler with low combustion chamber loading (1.2 MW/m3) — clean combustion with low nitrogen oxide emissions
  • High level of serviceability through large cleaning door
  • Load-bearing cover on top of the boiler as part of the standard delivery — this simplifies installation and maintenance
  • Economical and safe operation of heating systems through the digital Vitotronic control system with communication capability. Standardised LON BUS for optional complete integration into building management systems
  • Approval in accordance with the European Pressure Equipment Directive 97/23/EC or the Gas Equipment Directive 90/396/EEC